AQT Steam Vortex Flow Meter
The Apure AQT measures steam flow using vortex shedding behind a bluff body. Specify saturated or superheated steam and the required output quantity when selecting the meter and its compensation arrangement.
- High accuracy, wide measuring range
- Steam flow with application-specific density compensation
- A variety of optional structure form, pipe sections, plug-in, flange, etc.
Vortex frequency is related to velocity within the operating range. Line volumetric flow describes volume at operating conditions. Steam mass flow uses steam density at the measured state. For dry saturated steam, pressure or temperature can establish saturation density when the saturated state is known. For superheated steam, confirm the pressure and temperature inputs and the compensation method. Identify condensate and possible wet-steam operation when sizing the meter.
Installation and selection
Provide the steam state, normal and limiting absolute pressure and temperature, pipe size, minimum and maximum flow, and the units the control system expects. Confirm the straight runs, required compensation instruments and available outputs for the selected version.
The published series overview lists a −25 to +300 °C temperature interval, a range ratio up to 10:1, and general accuracy references of ±1.0% for liquid and ±1.5% for gas. Confirm the limits and accuracy basis for the selected steam configuration. The range table below retains the listed values. Verify the flow basis, steam state and operating conditions with Apure before using its entries for sizing.
Published range reference
| Nominal path(mm) | Flow range ( m³/h ) | ||
| liquid | gas | steam | |
| 25 | 0.8~12 | 7.2~60 | 12~120 |
| 40 | 2~30 | 18~180 | 30~300 |
| 50 | 3~45 | 20~300 | 50~500 |
| 65 | 6.5~84 | 54~540 | 84~840 |
| 80 | 10~130 | 70~700 | 120~1200 |
| 100 | 20~200 | 12~1200 | 200·2000 |
| 125 | 32~320 | 200~2000 | 320~3200 |
| 150 | 45~450 | 240~2400 | 440~4400 |
| 200 | 90~900 | 480~4800 | 800~8000 |
| 250 | 12~1200 | 740~7400 | 1200~12000 |
| 300 | 15~1500 | 1000~10000 | 1780~17800 |
| Brand | Apure |
|---|---|
| Model | AQT |
| Listed accuracy | 1.0% |
| Nominal diameter | DN15~DN300 |
| Material | Stainless Steel |
| Signal output | 4~20mA |
| Connection | Flange connection |
| Repeatability | 0.3% |
| Listed power options | +12VDC ~ 36VDC, 3.6V Lithium battery |