AK2000E Ultrasonic Liquid Level Sensor

The Apure AK2000E measures liquid level without contacting the liquid. Mount the ultrasonic sensor above the surface with a clear path for the echo.

  • Non-contact liquid level
  • Ultrasonic echo measurement
  • Level or distance display

Measuring level with ultrasound

The sensor emits a sound pulse through the air space and measures the time it takes for the echo to return from the liquid surface. The instrument converts that time to distance. Set the empty reference so that the indicated level is based on the required tank datum.

Mounting and first reading

Keep the maximum liquid level outside the specified dead zone and check that the lowest liquid level is within the usable distance range. Aim the sensor at the liquid surface and keep pipes, ladders and inlet streams out of its beam. Heavy foam, condensation or a disturbed surface can weaken the echo. Compare the displayed distance with a known distance after installation.

Confirm which listed distance range is supplied. Check the dead zone, pressure reference, temperature and output configuration against the tank and its highest and lowest expected levels. The earlier overview listed a 4–20 mA analog output and 2 relays. Verify these against the ordered wiring diagram.

BrandApure
ModelAK2000E
Measuring range0-10M 0-20M
StructureIntegrated type
Deadzone0.5m
Resolution1mm
Range accuracy±3mm(standard conditions)
Working temperature-20~60℃
Pressure≤ 3 atmospheres
DisplayBuilt-in LCD display level or space distance