A10 EC Electrical Conductivity Meter

Apure A10 EC Electrical Conductivity Meter is intelligent upgrade product of ES-2200 industrial conductivity instrument. The electrical conductivity (TDS) value of various industrial water can be continuously measured and controlled. The device is widely used in scientific experiment equipment, chemical, pharmaceutical, environmental protection, metallurgy, papermaking, food, beverage and water supply industries.

  • Easy to operate
  • Widely used
  • Automation

Apure A10 EC Electrical Conductivity Meter is intelligent upgrade product of ES-2200 industrial conductivity instrument. The electrical conductivity (TDS) value of various industrial water can be continuously measured and controlled. The device is widely used in scientific experiment equipment, chemical, pharmaceutical, environmental protection, metallurgy, papermaking, food, beverage and water supply industries.

Measuring0.01 electrode:0.02 to 20.00us/cm
Range0.1 electrode:0.2 to 200.0us/cm
1.0 electrode:2-2000us/cm
10.0 electrode:20 to 20000us/cm
Accuracy±1%FS
Stability±1%FS/24H
TemperatureCompensation range:-10~130℃.NTC10K
CompensationPT1000 or PT100,accuracy:±0.5℃
display2.4inch LCD display
Relay out2 ralay out,capacity:250VAC,3A
Signal output4-20mA output,RS485 communictaion,compatible
with standad MODBUS-RTU
Power supplyAC220±10%,50HZ
Dimensions96*96*93mm(H*W*D)

Characteristics:

  • Factory standard configuration is Chinese interface, can be switched to English in the language menu.
  • Conductivity (TDS) and temperature measurement, upper limit control, current output and digital communication.
  • It can be free to adjust the conductivity temperature compensation coefficient and TDS conversion coefficient.
  • Two relays, conductivity (TDS) and temperature can be controlled respectively, and the hysteresis can be adjusted freely.
  • In a set of instrument mode isolation transmission port can be configured with electrical conductivity (TDS) or temperature, the maximum loop resistance of 300 Ω.
  • Voice alarm switch function, through the interface options setting on or off.
  • LCD backlight can choose energy-saving mode, auto off timer.
  • High performance CPU, excellent electromagnetic compatibility.
  • One click restore factory parameter function.
  • Password management functions, prevent misuse of non professional personnel.

Correspondence between TDS and conductivity

EC (us/cm)TDS (ppm)EC (us/cm)TDS (ppm)EC (us/cm)TDS (ppm)
0.107535.3650305.5
0.20.110047700329
0.50.212558.8750352.5
10.515070.5800376
1.50.717582.3850399.5
20.9275129.3900423
2.51.2300141950446.5
52.4350164.510004700
104.74001881250587.5
157450211.51500705
209.45002351750822.5
2511.8550258.52000940
5023.560028225001175
BrandApure
ModelA10
Temp compensationNTC10K/PT1000
Accuracy±1%(FS) +Digit
display2.4inch LCD display
Relay out2 ralay out,capacity:250VAC,3A
Power supplyAC220±10%,50HZ
Signal output4-20mA output,RS485 communictaion,compatible
Dimensions96*96*132mm
Cut off dimensions92.5*92.5mm